The perforated cable trays RGM 60 have sides 60 mm high and are available in widths from 100 to 600 mm. The standard length is 3000 mm. The cables have a material thickness of 1 mm. We provide components in various materials and surface finishes to ensure that the corrosion requirements are met for all sorts of applications.
The magnetic shielding attenuation is 22 dB without the cover and 30 dB with the cover.
Continously hot galvanized (Sendzimir process) (DIN EN 10346)
| width | length | t material thickness | QSKdistributed load control cable | A cross section area | weight | ||
|---|---|---|---|---|---|---|---|
| RGM 60-10S | 100 mm | 3000 mm | 1,00 mm | 0,09 kN/m | 57 cm² | 5,570 kg | |
| RGM 60-20S | 200 mm | 3000 mm | 1,00 mm | 0,17 kN/m | 117 cm² | 7,570 kg | |
| RGM 60-30S | 300 mm | 3000 mm | 1,00 mm | 0,26 kN/m | 177 cm² | 9,780 kg | |
| RGM 60-40S | 400 mm | 3000 mm | 1,00 mm | 0,34 kN/m | 237 cm² | 11,980 kg | |
| RGM 60-50S | 500 mm | 3000 mm | 1,00 mm | 0,43 kN/m | 297 cm² | 14,200 kg | |
| RGM 60-60S | 600 mm | 3000 mm | 1,00 mm | 0,52 kN/m | 357 cm² | 16,400 kg |
Hot-dip galvanized, according to BS 729 (DIN EN ISO 1461)
| width | length | t material thickness | QSKdistributed load control cable | A cross section area | weight | ||
|---|---|---|---|---|---|---|---|
| RGM 60-10F | 100 mm | 3000 mm | 1,00 mm | 0,09 kN/m | 57 cm² | 6,070 kg | |
| RGM 60-20F | 200 mm | 3000 mm | 1,00 mm | 0,17 kN/m | 117 cm² | 8,260 kg | |
| RGM 60-30F | 300 mm | 3000 mm | 1,00 mm | 0,26 kN/m | 177 cm² | 10,670 kg | |
| RGM 60-40F | 500 mm | 3000 mm | 1,00 mm | 0,34 kN/m | 237 cm² | 13,070 kg | |
| RGM 60-50F | 500 mm | 3000 mm | 1,00 mm | 0,43 kN/m | 297 cm² | 15,700 kg | |
| RGM 60-60F | 600 mm | 3000 mm | 1,00 mm | 0,52 kN/m | 357 cm² | 18,100 kg |
Stainless steel, according to ASTM 304 / BS 304 S 3
| width | length | t material thickness | QSKdistributed load control cable | A cross section area | weight | ||
|---|---|---|---|---|---|---|---|
| RGM 60-10E | 100 mm | 3000 mm | 1,00 mm | 0,09 kN/m | 57 cm² | 5,600 kg | |
| RGM 60-20E | 200 mm | 3000 mm | 1,00 mm | 0,17 kN/m | 117 cm² | 7,620 kg | |
| RGM 60-30E | 300 mm | 3000 mm | 1,00 mm | 0,26 kN/m | 177 cm² | 9,840 kg | |
| RGM 60-40E | 400 mm | 3000 mm | 1,00 mm | 0,34 kN/m | 237 cm² | 12,060 kg | |
| RGM 60-50E | 500 mm | 3000 mm | 1,00 mm | 0,43 kN/m | 297 cm² | 14,300 kg | |
| RGM 60-60E | 600 mm | 3000 mm | 1,00 mm | 0,52 kN/m | 357 cm² | 16,600 kg |
Stainless steel, according to ASTM 31 Ti / AISI 316 L, BS 320S17 / BS 316S11
| width | length | t material thickness | QSKdistributed load control cable | A cross section area | weight | ||
|---|---|---|---|---|---|---|---|
| RGM 60-10E4 | 100 mm | 3000 mm | 1,00 mm | 0,09 kN/m | 57 cm² | 5,670 kg | |
| RGM 60-20E4 | 200 mm | 3000 mm | 1,00 mm | 0,17 kN/m | 117 cm² | 7,720 kg | |
| RGM 60-30E4 | 300 mm | 3000 mm | 1,00 mm | 0,26 kN/m | 177 cm² | 9,960 kg | |
| RGM 60-40E4 | 400 mm | 3000 mm | 1,00 mm | 0,34 kN/m | 237 cm² | 12,210 kg | |
| RGM 60-50E4 | 500 mm | 3000 mm | 1,00 mm | 0,43 kN/m | 297 cm² | 14,333 kg | |
| RGM 60-60E4 | 600 mm | 3000 mm | 1,00 mm | 0,52 kN/m | 357 cm² | 16,550 kg |






Technical information cable trays
Cable trays - Complete catalogue
cable trays
Compact overview Cable trays
Safe working load (Cable tray RGM 60)